Control Concepts manufactures power filters, surge protection, and lightning protection products for companies having power quality issues
such as spikes, transients, and surges. Our patented Islatrol
Active Tracking® Filters, as well as our surge
protection products, are ideal for many applications.
Series-connected high-frequency noise filter available from 1/4
Amp PCB mount to 1,200 Amp 3-phase hard-wired. Ideal for those applications
where internally generated noise and transients are of concern.
Typical applications include industrial, medical, and telecommunications
equipment. DC options available.
The
original Active Tracking® Filter provides the industry’s
best IEEE Category “A” protection (most commonly
occurring transients). Typically reduces normal mode transients
to +/– 5 volts
Non-degrading,
series filter technology for total durability
Built
to meet your unique requirements. Available in a multitude of
voltage, phase, and packaging configurations
10-year
warranty
Input
Voltage
120 VAC Models
0–150
VRMS
240 VAC Models
0–275
VRMS
480 VAC Models
0–520
VRMS
Line
Frequency
50/60
Hz
(400 Hz Available)
Transient
Attenuation Response Time
Instantaneous
Mean
Time Between Failure (MTBF)
Greater
Than 100,000 Hours (MIL 217F)
Packaging
Single-phase
units through 30 Amps housed in black, high-impact
plastic case, vacuum impregnated magnetics, epoxy
encapsulated; single phase greater than 30 Amps,
480 VAC, and three phase units housed in NEMA
12 enclosures
Operating
Temperature
–40ºC
to +45ºC
Derate
Linearly to 60% at +70ºC
Load Surge Current Rating
10
mSec
5
x Nominal
1
sec
3
x Nominal
5 sec
2
x Nominal
Safety
Approvals
UL
1283 Listed or Recognized
CSA
Typical
Islatrol® Test Results
IEEE
Category A Ringwave 6 kV, 200A, 100 kHz
IEEE
Category B Ringwave 6 kV, 500A, 100 kHz
Normal
Mode
Normal
Mode
I-100
6.0
6.2
I-101
5.5
6.2
I-102
3.6
3.8
I-105
3.6
3.8
I-107
3.2
3.5
I-115
2.8
3.0
I-120
1.0
1.2
I-130
1.4
2.0
I-200
5.2
5.5
I-201
5.1
5.5
I-202
3.4
3.6
I-205
2.4
2.6
I-207
3.6
3.8
I-215
3.0
3.2
I-230
3.0
3.6
Note:
All measurements in volts. IEEE test results with no
AC applied. Normal mode—L-N or L1-L2.
Transient
Reduction
Minimum
of 40 dB from 50 kHz through 50 MHz. Attenuation
is greater than 50 dB to the surge withstand capability
ringwave test IEEE C62.41, Category “A”
and “B”
Load
Regulation
Better
than 1% from no load through full load
SINGLE-PHASE
MODELS
120
VAC Models with Barrier Strip at Input & Output / with Wire
Leads at Input & Output