Network Power Divisions: 
power filters Control Concepts





















RoHS Compliancy List

Control Concepts manufactures power filters, surge protection, and lightning protection products for companies having power quality issues such as spikes, transients, and surges. Our patented Islatrol Active Tracking® Filters, as well as our surge protection products, are ideal for many applications.





printable page



Series-connected DIN/flange mount high-frequency noise filter/surge suppressor. Ideal applications include critical industrial loads drawing up to 20 amps of continuous current. Typical applications include any microprocessor-based products, including industrial PLCs, OEM applications, and motion control systems.

Multi-staged design, combining a unique hybrid clamping network with the Active Tracking Technology of the Islatrol® family
Surge current capacity—45,000 Amps
Transient protection in all modes: line to neutral, line to ground, and neutral to ground
LED status indication and form C contact for remote indication
DIN mountable enclosure
UL 1449, 1283, CUL recognized, CE
10-year warranty
 

MCOV

  120 Volt
150 VRMS
  240 Volt
275 VRMS
Line Frequency
47–63 Hz
Connection
Terminal
Mounting Type
DIN/Flange
Weight
< 3 lbs
Response Time
  Normal Mode
< 0.5 ns
  Common Mode
< 5 ns
Operating Temperature
–40ºC to +45ºC
  Derate Linearly to 60% at +70ºC
Operating Humidity
0% to 95%

UL 1449 Classification

  120V Normal Mode
330 Volts
  120V Common Mode
400 Volts
  240V Normal Mode
600 Volts
  240V Common Mode
800 Volts
Peak Surge Current Capability (8 x 20 µs)
  Line to Neutral
15,000 Amps
  Line to Ground
15,000 Amps
  Neutral to Ground
15,000 Amps
  Total
45,000 Amps
Frequency Response (Forward-Reverse)
  Normal Mode
10 kHz to 50 MHz—
90 dB Min
  Common Mode
5 MHz to 50 MHz—
60 dB Min
Typical Category A Ringwave
(6 kV, 200A, 100 kHz)
Normal Mode/Common Mode
  3 Amp
1V / 300V
  5 Amp
0.7V / 292V
  10 Amp
0.7V / 300V
  20 Amp
0.7V / 300V
Typical Category B Ringwave
(6 kV, 500A, 100 kHz)
Normal Mode/Common Mode
  3 Amp
178V / 300V
  5 Amp
162V / 291V
  10 Amp
153V / 300V
  20 Amp
200V / 300V
Voltage*
Continuous Current
Model
120V
3 Amps
IE-103
120V
5 Amps
IE-105
120V
10 Amps
IE-110
120V
20 Amps
IE-120
240V
3 Amps
IE-203
240V
5 Amps
IE-205
240V
10 Amps
IE-210
240V
20 Amps
IE-220
* All voltage configurations are single phase—2 wire + gnd.


Copyright © 2005 Control Concepts Corporation
Notice and Conditions | Contacts