| Operating
Voltage Range |
+/– 15%
|
| Fault
Current Rating (AIC) |
65
kAIC
|
| Operating
Frequency Range |
47–63
Hz
|
| Capacity |
Continuous
|
| 50 Ω EMI/RFI
Attenuation |
40
dB
|
Dry
Contact Rating
(100-2
only) |
125
VAC, 8A,
1.0 pf
|
| Response
Time |
< 0.5
ns
|
| Operating
Temperature |
–45°C
to +50°C
|
| Operating
Humidity |
0%
to 95%
|
| Certifications |
UL
1449, CUL
|
| Warranty |
5
Year
|
|
Clamping
UL 1449 Classification* |
| 120/208 |
| |
Line
to Neutral |
400
Volts
|
|
|
Line
to Line |
800
Volts
|
| |
Line
to Ground |
400
Volts
|
| |
Neutral
to Ground |
400
Volts
|
| 277/480 |
| |
Line
to Neutral |
800
Volts
|
| |
Line
to Line |
1,500
Volts
|
| |
Line
to Ground |
800
Volts
|
| |
Neutral
to Ground |
800
Volts
|
| 480 |
| |
Line
to Line |
1,500
Volts
|
| |
Line
to Ground |
1,500
Volts
|
*
UL classifications for other voltages
available upon request.
Peak
Surge Current Capability
(8 x 20 µs) |
| Model:
IMxxxx160 |
| |
Phase: |
160,000
Amps
|
| |
L-N: |
80,000
Amps
|
| |
L-L: |
80,000
Amps
|
| |
L-G: |
80,000
Amps
|
| |
N-G: |
80,000
Amps
|
| Model:
IMxxxx100-2 |
| |
Phase: |
100,000
Amps
|
| |
L-N: |
100,000
Amps
|
| |
L-L: |
100,000
Amps
|
| |
L-G: |
N
/ A
|
| |
N-G: |
100,000
Amps
|
|