| Operating
Voltage Range |
+/– 15%
|
| Fault
Current Rating (AIC) |
200
kAIC
|
| Operating
Frequency Range |
47–63
Hz
|
| Capacity |
Continuous
|
| 50 Ω EMI/RFI
Attenuation |
50
dB
|
| Response
Time |
< 0.5
ns
|
| Operating
Temperature |
–40°C
to +50°C
|
| Operating
Humidity |
0%
to 95%
|
| Certifications |
UL
1449,
1283 CUL
|
| Warranty |
5
Year
|
|
| Clamping |
| UL
1449 Classification* |
| 120/208 |
| |
Line
to Neutral |
400
Volts
|
| |
Line
to Line |
800
Volts
|
| |
Line
to Ground |
400
Volts
|
| |
Neutral
to Ground |
400
Volts
|
| 277/480 |
| |
Line
to Neutral |
800
Volts
|
| |
Line
to Line |
1,500
Volts
|
| |
Line
to Ground |
800
Volts
|
| |
Neutral
to Ground |
800
Volts
|
| 480 |
| |
Line
to Line |
1,500
Volts
|
| |
Line
to Ground |
1,500
Volts
|
*
UL classifications for other voltages
available upon request.
| Peak
Surge Current Capability (8 x 20 µs) |
| Model:
IHxxxx400 |
| |
Phase: |
400,000
Amps
|
| |
L-N: |
200,000
Amps
|
| |
L-L: |
200,000
Amps
|
| |
L-G: |
200,000
Amps
|
| |
N-G: |
200,000
Amps
|
| Model:
IHxxxx200 |
| |
Phase: |
200,000
Amps
|
| |
L-N: |
100,000
Amps
|
| |
L-L: |
100,000
Amps
|
| |
L-G: |
100,000
Amps
|
| |
N-G: |
100,000
Amps
|
| Model:
IHxxxx200-2 |
| |
Phase: |
200,000
Amps
|
| |
L-N: |
200,000
Amps
|
| |
L-L: |
200,000
Amps
|
| |
L-G: |
N/A
|
| |
N-G: |
200,000
Amps
|
| Model:
IHxxxx100-2 |
| |
Phase: |
100,000
Amps
|
| |
L-N: |
100,000
Amps
|
| |
L-L: |
100,000
Amps
|
| |
L-G: |
N/A
|
| |
N-G: |
100,000
Amps
|
|