Input
Voltage
|
| 120
VAC Models |
0–150
VRMS
|
| 240
VAC Models |
0–275
VRMS
|
| 480
VAC Models |
0–520
VRMS
|
| Line
Frequency |
50/60
Hz
(400 Hz Available)
|
| Transient
Attenuation Response Time |
|
Instantaneous
|
| Mean
Time Between Failure (MTBF) |
|
Greater
Than 100,000 Hours (MIL 217F)
|
| Packaging |
| Single-phase
units through 30 Amps housed in black, high-impact
plastic case, vacuum impregnated magnetics, epoxy
encapsulated; single phase greater than 30 Amps,
480 VAC, and three phase units housed in NEMA 12
enclosures |
|
| Operating
Temperature |
–40ºC
to +45ºC
|
Derate
Linearly to 60% at +70ºC
|
Load
Surge Current Rating
|
| 10
mSec |
5
x Nominal
|
| 1
sec |
3
x Nominal
|
| 5
sec |
2
x Nominal
|
| Safety
Approvals |
|
UL
1283 Listed or Recognized
|
|
CSA
|
|
| Typical
Islatrol® Test Results |
| |
IEEE
Category A Ringwave 6 kV, 200A, 100 kHz
|
IEEE
Category B Ringwave 6 kV, 500A, 100 kHz
|
| |
Normal
Mode
|
Normal
Mode
|
| I-100 |
6.0
|
6.2
|
| I-101 |
5.5
|
6.2
|
| I-102 |
3.6
|
3.8
|
| I-105 |
3.6
|
3.8
|
| I-107 |
3.2
|
3.5
|
| I-115 |
2.8
|
3.0
|
| I-120 |
1.0
|
1.2
|
| I-130 |
1.4
|
2.0
|
| I-200 |
5.2
|
5.5
|
| I-201 |
5.1
|
5.5
|
| I-202 |
3.4
|
3.6
|
| I-205 |
2.4
|
2.6
|
| I-207 |
3.6
|
3.8
|
| I-215 |
3.0
|
3.2
|
| I-230 |
3.0
|
3.6
|
Note:
All measurements in volts. IEEE test results with no
AC applied. Normal mode—L-N or L1-L2.
|
| Transient
Reduction |
| Minimum
of 40 dB from 50 kHz through 50 MHz. Attenuation
is greater than 50 dB to the surge withstand capability
ringwave test IEEE C62.41, Category “A” and “B” |
|
| Load
Regulation |
| Better
than 1% from no load through full load |
|